Plenty of small offices around York and Harrogate get everything tested every twelve months because that is what happened last time, and because the label on the kettle carries a date that makes the next booking obvious. Annual testing of the whole office is a defensible choice. It is not, however, a legal interval, because nothing in UK law sets a frequency for any appliance.

Where the interval comes from

Regulation 4(2) of the Electricity at Work Regulations 1989 requires electrical systems to be maintained, so far as is reasonably practicable, to prevent danger. It says nothing about testing, labels or twelve-month cycles. The Provision and Use of Work Equipment Regulations 1998 add a duty to keep work equipment in efficient working order and good repair. Between them, the two sets of regulations leave the interval to the duty holder, which in a small office normally means the employer, and they expect that interval to be based on risk.

The HSE's guidance for offices and similar premises is INDG236, Maintaining portable electric equipment in low-risk environments, with HSG107 covering the more arduous end of the scale. The IET's Code of Practice for In-service Inspection and Testing of Electrical Equipment, now in its 5th edition, moved in the same direction. It dropped the fixed frequency table that the 4th edition carried and replaced it with a risk assessment built around four things: the environment the equipment sits in, the users and whether they report damage, the construction of the equipment, and whether it is hand-held or rarely moved.

Three different checks, three different frequencies

Both the HSE and the IET split maintenance into three levels, and mixing them up is where most confusion about frequency starts. A user check is someone looking at the lead and plug before they use something, which costs nothing and needs no electrician. A formal visual inspection is a competent person examining the equipment and the plug properly, without test instruments. A combined inspection and test is the visual inspection plus the instrument work: earth continuity, insulation resistance and so on. That last one is the part people mean when they say PAT testing, and it is the least frequent of the three.

What that means for a typical office

A desktop computer, a monitor or a printer that sits in one place and gets moved when the desks are rearranged is about as low-risk as mains equipment gets. HSE guidance for low-risk environments suggests a formal visual inspection every two to four years for that sort of item, with combined inspection and testing only up to around every five years for earthed equipment, and not necessarily needed at all for double-insulated kit.

The kitchen is a different matter. A kettle is earthed Class I equipment, it gets handled several times a day, it lives near water, and its flex takes real abuse. For that category the suggested starting point is a user check, a formal visual inspection roughly every six months and a combined inspection and test every one to two years. Extension leads and detachable mains leads follow whatever they are plugged into, and in most offices the four-way under someone's desk with a heater on it is the item most likely to fail.

Why one annual visit often still makes sense

INDG236 is explicit that you can inspect and test everything at the same time if that is easier to manage, provided you use the shortest interval in the group rather than the longest. In a small office with 30 to 60 items, that is usually the sensible answer. Running three separate cycles for computers, kitchen appliances and leads generates more admin than it saves, and our PAT testing visits are priced by time on site rather than per item, so an office of that size is normally an up-to-an-hour or half-day job either way, from £50 or from £125.

There are also reasons an office ends up on an annual cycle regardless of the risk assessment. Some insurance schedules and commercial leases specify annual testing of tenant equipment, and some public sector frameworks and client audits ask for a certificate dated within the last twelve months. If a contract says annual, the contract decides. Letting and estate agency offices in particular often find it simplest to test their own office kit on the same annual visit that covers the appliances in their managed rental properties.

Reviewing the interval after the first cycle

Whatever frequency you start on, the results should feed back into it. If a full test of your office produces no failures beyond a couple of rewired plugs, you have written evidence for extending the interval on the low-risk items next time. If the same portable heaters and extension leads keep failing, that argues for shortening it, or for replacing the leads. Keep the asset register and the previous results, because the register is what makes the next decision defensible rather than a guess. We cover offices across York, Harrogate, Selby and the surrounding area, usually in a single visit.

Frequently Asked Questions

How often should office equipment be PAT tested?
There is no legally fixed interval. HSE guidance for low-risk environments such as offices suggests that rarely moved items like desktop computers and printers need a formal visual inspection every two to four years, with combined inspection and testing only up to around every five years, while frequently handled earthed items like kettles are suggested at a six-monthly visual inspection and a combined inspection and test every one to two years. Many small offices simply test everything annually because it is easier to manage and because insurers or clients ask for a current certificate.

Is annual PAT testing a legal requirement for a small business in the UK?
No. The Electricity at Work Regulations 1989 require electrical equipment to be maintained so as to prevent danger, and the Provision and Use of Work Equipment Regulations 1998 require work equipment to be kept in good repair, but neither sets a testing frequency or mentions PAT testing by name. The interval is for the duty holder to set based on risk, using guidance such as HSE INDG236 and the IET Code of Practice. Annual testing is common practice, not law.

Do we need to PAT test laptops, phone chargers and other items staff bring into the office?
If employee-owned equipment is used for work on your premises, it comes within your duty to prevent danger and should be brought into your inspection regime or else prohibited by a written policy. Chargers, desk fans, heaters and personal kettles are the usual culprits, and cheap unbranded chargers are a common reason for refusing an item rather than testing it. Battery-powered devices themselves cannot be meaningfully PAT tested, so the check focuses on the charger and its lead.

In a leased or serviced office, who is responsible for PAT testing?
Responsibility follows ownership and control of the equipment, so as an employer you are normally the duty holder for the appliances your business brings in and uses. The building owner or managing agent is usually responsible for the fixed electrical installation and for equipment in common areas such as shared kitchens and printers. Check the lease or licence, because some agreements specifically require tenants to hold current test records for their own equipment.

How long does it take to PAT test a small office?
An office with roughly 30 to 60 items is typically an hour to a half-day, depending on how much is packed under desks and how much has to be worked around while people are using it. We price by visit length rather than per item, starting from £50 for up to an hour and from £125 for a half-day. Clearing access to sockets and extension leads beforehand is the single thing that speeds a visit up most.